If you run a licensed assisted living facility in Texas, your fire alarm is on a tighter schedule than most buildings. State rules require a local fire marshal inspection at least once every 12 months. They also require the fire alarm system to be inspected, tested, and maintained at least once every six months, by a company registered with the State Fire Marshal's Office.

That's the short answer. The rest of this post covers why the schedule is tighter, how your license type changes the system you need, how locked memory care doors have to work with the fire alarm, and what Houston-area facilities should have ready before the next inspection.

How often does an assisted living facility in Texas need a fire alarm inspection?

At least every six months. Texas Health and Human Services (HHSC) licenses assisted living facilities under 26 TAC Chapter 553. The rule on safety operations, §553.104, says three things about fire protection:

  • Fire marshal inspection: at least once every 12 months, by the local fire marshal. Where there's no local fire marshal, the State Fire Marshal's Office does it.
  • Fire alarm inspection, testing, and maintenance: a program that follows NFPA 72, carried out at least once every six months. The facility must contract with a company that holds an Alarm Certificate of Registration from the State Fire Marshal's Office.
  • Fire sprinklers, if you have them: the same six-month schedule, with a company holding a sprinkler certificate of registration.

Many commercial buildings schedule a full fire alarm inspection once a year. Our post on how often a commercial fire alarm has to be inspected in Texas explains that general schedule. Assisted living is held to twice that.

Why assisted living fire safety rules are stricter

Many residents can't get out quickly on their own. Some use walkers or wheelchairs. Some are on oxygen. Some have memory loss and won't follow an alarm to an exit. Every minute between the first sign of smoke and the alarm sounding matters more here than in an office.

National news showed what's at stake. On July 13, 2025, a fire at Gabriel House, an assisted living residence in Fall River, Massachusetts, killed ten residents. The Massachusetts Department of Fire Services classified the cause as undetermined. It said medical oxygen in the building "played a significant role in the fire's rapid spread."

The fire alarm can't prevent a fire. Its job is to buy time for staff and firefighters. That's why Texas checks it so often.

Type A vs. Type B: how your license type changes the fire alarm system

Texas licenses two main types of assisted living facility, defined in §553.5:

  • Type A: residents must be able to evacuate without physical help from staff, and must be able to follow directions in an emergency.
  • Type B: residents may need staff help to evacuate, may need care at night, and may not be able to follow emergency directions.

That difference drives the fire protection rules. The exact requirements also depend on whether the building is small or large, and whether it's existing or new construction. Each combination has its own section in Subchapter D. Two examples:

  • A new small Type A facility needs a manual fire alarm system, plus smoke detectors in bedrooms, corridors, living rooms, dining rooms, offices, and other listed areas (§553.215).
  • An existing large Type B facility needs smoke detectors in corridors, a full NFPA 13 sprinkler system, emergency backup power for the fire alarm, and a fire alarm that automatically notifies emergency forces (§553.145). In apartments with their own kitchens, smoke detectors sound only inside the unit. A heat detector in the kitchen sets off the building-wide alarm.

If you're buying a building, converting one, or changing your license type, check which section applies before you budget. A building that works for Type A may need a lot more for Type B.

Memory care doors: how locked doors and the fire alarm work together

Memory care units are often locked so residents can't wander off. Texas allows that in certified Alzheimer's units, but the locks have to give way in an emergency. Under the current rule for Alzheimer's units, §553.311:

  • Locks on control doors must be electronic, and must release when the fire alarm or sprinkler system activates, when the facility loses power, or when staff press a release switch at the monitoring station or main staff station.
  • Exit door locks must be electromagnetic, with no throw-bolts. A manual fire alarm pull station must be within five feet of each exit door, with a sign reading "Pull to release door in an emergency."
  • Staff must be trained on how to release the doors.
  • If the secured outdoor area's gate nearest the building exit is locked, it must use an electronic lock.

This is where your fire alarm and your access control system depend on each other. A door that doesn't release when the alarm sounds is a serious problem. A door that releases when it shouldn't is a different kind of problem. Ask your fire alarm company to test the door releases during each six-month visit and write down the results.

Who is allowed to inspect and test your fire alarm in Texas?

A company registered with the State Fire Marshal's Office. Under Texas law, that registration covers inspecting and testing, not just installing. §553.104 also requires assisted living facilities to use a registered company specifically. Our post on who licenses fire alarm companies in Texas and how to check yours walks through the free lookup.

Who does this work in Houston. DSC inspects, tests, services, and installs commercial fire alarm systems in Houston, including in assisted living and memory care buildings, where fire alarm and door access control have to work as one system. DSC holds Texas State Fire Marshal's Office Alarm Certificate of Registration ACR-1930865, and is an authorized dealer and certified installer for Edwards, Honeywell, and Siemens fire alarm systems. Learn more about our fire alarm inspection services.

What HHSC's proposed 2026 rule changes would mean

In September 2026, HHSC proposed a broad rewrite of the assisted living rules. It was published in the Texas Register on September 4, 2026. According to HHSC's summary, the proposal would:

  • Remove the "contract" and "program" language for fire safety system upkeep. Instead, facilities would have to make sure inspection, testing, and maintenance are "performed by a qualified individual," and keep the records onsite.
  • Move the memory care construction rules, including the door-locking rules, from §553.311 into a new §553.250.
  • Clarify fire alarm power supply requirements, and allow smoke alarms or smoke detectors in resident units with their own cooking equipment.

HHSC's own explanation notes that the Texas Department of Insurance still requires certain fire alarm work to be done by licensed people. So the practical answer doesn't change. Your fire alarm still needs a registered company. You just may not need a standing contract to prove it.

As of November 16, 2026, these are proposals. Until HHSC adopts final rules, the current rule stands. Watch for the final version, or ask your licensing contact.

Houston and Harris County: your fire marshal and backup power

The fire marshal inspection required by §553.104 is done by whoever has fire code authority where your building sits. Inside Houston city limits, that's the Houston Fire Department's Fire Marshal's Office. The City also issues a fire alarm permit, and its ordinance exempts only single-family homes.

Outside the city, in areas where the Harris County Fire Marshal's Office has authority, there's an added requirement. Its backup power FAQ says assisted living and nursing facilities needed backup power in place by January 1, 2026. The backup has to run critical systems, including the fire alarm system and electrically operated locks on egress doors. The county says it checks compliance during annual fire inspections. The rule followed Hurricane Beryl, when the county counted about 200 heat-related illnesses and 11 deaths.

If your memory care doors run on electric locks, this is worth a close look. The backup power needs to keep those doors working the way your plan says they should.

What to have ready before your next fire marshal or HHSC visit

Use this list whether you run a 16-bed Type A home or a 120-unit campus with memory care:

  1. Your last two fire alarm inspection reports, no more than six months apart.
  2. Sprinkler inspection reports, on the same schedule, if you have sprinklers.
  3. Your fire alarm company's Alarm Certificate of Registration number, checked against the State Fire Marshal's lookup.
  4. A record of every deficiency from the last report, and when and how each one was fixed.
  5. Door release test results for every memory care control door, exit door, and secured gate.
  6. Staff training records on releasing memory care doors.
  7. Your current fire marshal inspection, dated within the last 12 months.
  8. Your City of Houston fire alarm permit, if you're inside city limits.
  9. Backup power documentation, if you're under the Harris County Fire Marshal.
  10. Your license type and building section (for example, existing large Type B under §553.145), so you know which rules you're being checked against.

If you're switching fire alarm inspection companies, get copies of the old reports before the handoff. A gap in the six-month cycle is easy to miss and hard to explain.

Nursing homes follow different rules

This post covers HHSC-licensed assisted living. Nursing facilities that take Medicare or Medicaid also answer to federal fire safety rules under 42 CFR §483.90, which adopt the 2012 edition of the NFPA 101 Life Safety Code. That's a different set of requirements, and a different post.

A fire alarm schedule you can keep

The six-month cycle isn't hard to follow once it's on the calendar. The trouble usually starts with a missed visit, a deficiency nobody closed, or a memory care door nobody tested. Those are all fixable before an inspector finds them.

If you'd like help sorting out what your building needs, or want a second look at your memory care door releases, reach out to DSC. We're glad to walk your Houston-area community and talk it through.

How to Switch Fire Alarm Inspection Companies in Houston Without a Compliance Gap

How to Switch Fire Alarm Inspection Companies in Houston Without a Compliance Gap

If your fire alarm inspection company misses visits, sends deficiency reports with no prices, or stops calling back, you can switch. The safest time...

Read More
Houston Apartment Fires: Does Your Complex Have a Fire Alarm System or Just Smoke Alarms?

Houston Apartment Fires: Does Your Complex Have a Fire Alarm System or Just Smoke Alarms?

On the afternoon of October 16, 2026, a fire started on a second-floor balcony at an apartment complex on Forum Park Drive in southwest Houston. Wind...

Read More
How Often Does a Commercial Fire Alarm Have to Be Inspected in Texas?

How Often Does a Commercial Fire Alarm Have to Be Inspected in Texas?

A commercial fire alarm system in the Houston area is tested at least once a year. That is the baseline most building owners know.

Read More